WAFER & GLOBE SILENT CHECK VALVES
580 & 581
SERIES
INSTALLATION / OPERATION / MAINTENANCE
Note 1: flanged gasket
must bridge this joint
for pressure seal
Installed with name plate here
6
2
34
5
1
OPERATION:
Cla-Val Silent Check Valves operate automatically, to open...
when pump flow starts and close silently ...when pump flow
stops.
INSTALLATION:
Silent Check Valves, Wafer and Globe style must be
installed between flat faced iron or steel flanges per ANSI
B16.5 or Awwa 207, utilizing a full faced gasket to bridge the
joint between the seat O.D. (2) and the body (1) flange face.
In this manner a pressure seal at this joint is made (see
Note 1). Install the valve so that the nameplate data is plain-
ly read and the flow arrow points in the flow direction.
Detail
1
2
3
4
5
6
Description
Body
Seat*
Disc*
Spring*
Bushing*
Screw*
Material
Cast Iron
Bronze or SS
Bronze or SS
(Optional Buna-N
®
)
Stainless Steel
Bronze
Stainless Steel
(3” & larger valves)
* Recommended Spare Part Kit
Note 2: All size 2” and 2 1/2” valves have
threaded seats in liev of screws
FLOW OPEN
See
Note 2
SERIES 580
WAFER STYLE CHECK VALVE
2" THRU 10"
1
2
6
3
4
5
Series 581
Globe Style
Check Valve
2” thru 42”
MAINTENANCE:
Cla-Val Silent Check Valves are ruggedly designed for years of trouble-free
service. Therefore, regular maintenance is not required. However, during
initial start-up period the following problems may surface (due to mis-application)
that can be easily resolved:
A. No Flow thru Valve:
1. Observe that the flow arrow name plate, on the
valve body, is pointing in the direction of flow.
2. Check that the down stream shut-off valve is full open.
B. Valve Chatters:
1. Confirm that the flow velocity is a minimum 3’/Sec.
2. Check that there is a minimum of 3 diameters of
straight pipe installed up stream of the silent check valve.
C. Valve Leakage:
1. Confirm a full face gasket is installed per Note 1.
A
MAXIMUM ALLOWABLE INSIDE
DIAMETER OF FLANGE
(SEE NOTE NO. 1 )
VALVE SEAT
VALVE DISC
VALVE BOD
Y
ANSI B16.5 COMPANION
FLANGE WITH FLAT FACE
MAXIMUM ALLOWABLE INSIDE
DIAMETER OF FLANGE
(SEE NOTE No. 1)
VALVE
SIZE
A
VALVE
SIZE
A
2
1
⁄2 2.940 14 14.140
3 3.570 16 16.160
4 4.570 18 18.180
5 5.660 20 20.200
6 6.720 24 24.250
8 8.720 30 30.250
10 10.880 36 36.250
12 12.880 42 42.250
STANDARD RING GASKET DIMENSIONS (SEE NOTE No. 2)
Valve
Size
I.D. For
125 Lb.
and
250 Lb.
Gasket
O.D. for
125 Lb.
Gasket
O.D. for
250 Lb.
Gasket
Valve
Size
I.D. For
125 Lb.
and
250 Lb.
Gasket
O.D. for
125 Lb.
Gasket
O.D. for
250 Lb.
Gasket
2
1
2 2.875 4.875 5.125 14 14.000 17.750 19.125
3 3.50 5.375 5.875 16 16.000 20.250 21.250
4 4,50 6.875 7.125 18 18.00 21.625 23.500
5 5.562 7.750 8.500 20 20.00 23.875 25.750
6 6.625 8.75 9.875 24 24.000 28.250 30.500
8 8.625 11.000 12.125 30 30.000 34.750 37.500
10 10.750 13.375 14.250 36 36.000 41.250 44.000
12 12.750 16.125 16.625 42 42.000 48.000 50.750
Note No. 1 - The mating companion flange I.D. must overlap the Valve seat.
This is required to achieve a seal between the seat O.D. and
The Body I.D. Interface area.
Silent Check Valve - Flanged or Wafer Style
(Flanged Style Shown)
Ring or Full Faxe Gasket
(1/16" Maximum Thickness)
Page view 0
1 2

Summary of Contents

Page 1 - 2” thru 42”

WAFER & GLOBE SILENT CHECK VALVES580 & 581SERIESINSTALLATION / OPERATION / MAINTENANCENote 1: flanged gasketmust bridge this joint for pressur

Page 2 - Closed

1. Shut off pump and pressure upstream and shut off isolation valve downstreamto completely isolate check valve. A skilled pipe fitter should be used

Related models: 581 Series Quick Manual

Comments to this Manuals

No comments